How to Setup and Configure the Pumps
- Open the Wrench app and select the connected pump.
- Go to the Performance tab to view the current control curve (e.g., 80 GPM at 30 ft head).
- If the curve doesn’t match site conditions, tap Configuration Settings.
- Navigate to Control Settings → Control and Design.
- From the Control Mode drop-down, select the appropriate control type.
- For sensorless modes, adjust the values for Design Flow, Design Head, and Zero Flow Head.
- Tap Save Configuration to apply the changes.
- Return to the Performance tab to confirm the updated curve.